Low temperature water cooled condensing unit
The low temperature water cooled condensing unit has the advantages of high efficiency and low noise level, and it is designed to meet the needs of low-temperature cooling. The unit adopts environmental protection refrigerants such as R404A and R507, which meets global environmental protection standards. The intelligent control system of the unit ensures stable operation, automatic safety protection and energy saving performance. The advanced technology and excellent performance of low-temperature water-cooled condensing units can provide customers with efficient, reliable and cost-effective refrigeration solutions.
Transporting & Installation
◆ Limitation
The condensing unit installation should be satisfy the safety rules of your country. The condensing unit is designed under the safety rules, if you need to obey the safety rules at your local site , and need to add some parts , the users have to bear the additional cost
◆ Installation location:
Please choose the suitable installation location as follows:
1.The unit must be installed outside the building in a location with good ventilation and smooth exhaust, and should be installed on level ground and a solid support.
2.The condensing unit and the air cooler should be as close to each other as possible to minimize the height difference between the compression condensing unit and the air cooler and the number of elbows in the pipes.
3.Avoid placing the condensing unit under a window or between buildings, or operating noise will be transmitted indoors.
4.There should be no strong heat sources, exhaust outlets of other equipment, steam and flammable gases around the unit.
5.There should be appropriate space around the unit for normal operation and maintenance. Rubber pads should be added between the frame and the support during installation to reduce the spread of vibration.
◆ Lifting and transporting
Pay attention to the safety of personnel and equipment when transporting the unit. When transporting, the inclination of the unit should be less than 30°. Do not remove the packaging before approaching the installation site.
◆ Maintenance space
When installation , please leave much space for operate and maintenance of condensing unit.
|
Refrigeration unit with Frascold screw compressors |
|||||
|
Unit model |
MFRLGF2- |
MFRLGF2- |
MFRLGF2- |
||
|
Refrigerant |
R507(R404A) |
||||
|
Power supply |
380V/3P/50HZ |
||||
|
Compressor |
Model |
FVR-L-110-380Y |
FVR-L-125-430Y |
FVR-L-160-540Y |
|
|
Qty |
2 |
2 |
2 |
||
|
Evaporating Temperature |
-50℃~-10℃ |
||||
|
Evap. Temp |
-25℃ |
Cooling capacity(KW) |
344.4 |
406.6 |
480.2 |
|
-25℃ |
Power input(KW) |
173.2 |
202.8 |
245.2 |
|
|
-42℃ |
Cooling capacity(KW) |
167.8 |
194.6 |
232.2 |
|
|
-42℃ |
Power input(KW) |
143.4 |
166.6 |
210.8 |
|
|
Liquid pipe(mm) |
DN50 |
DN50 |
DN50 |
||
|
Suction pipe(mm) |
DN125 |
DN150 |
DN150 |
||
|
Oil separator outlet(mm) |
DN80 |
DN80 |
DN80 |
||
|
Receiver inlet(mm) |
DN65 |
DN65 |
DN65 |
||
|
Overall size |
L(mm) |
2600 |
3200 |
3200 |
|
|
W(mm) |
1950 |
2100 |
2100 |
||
|
H(mm) |
1800 |
2200 |
2200 |
||
|
cooling capacity and power are set based on condensing temperature of 35℃,used for evaporation condenser. |
|||||
FAQ
Q: Are you a factory or trading company?
A: We are a comprehensive refrigeration equipment factory, we produce the air cooled and water cooled condensing unit, water chiller, evaporators, air condensers. We cooperate with many international compressor brands, such as Bitzer, Mycom, GEA, Frascold, Hanbell and others.
Q: Do you have any after-sales service for export orders?
A: We are working with some customers for after-sales service and also you can cooperate with us as an agent and after-sales service center.








Hot Tags: low temperature water cooled condensing unit, China low temperature water cooled condensing unit manufacturers, suppliers, factory, condensing unit for food refrigeration, commercial condensing unit for refrigeration, refrigeration machinery condensing unit, cooling system condensing unit, water cooled cooling condensing unit, commercial refrigeration compressor unit